two-stage surge protection for Ethernet networks,
for the protection of Ethernet Cat. 6 with PoE (Power over Ethernet) Mode A, B against surge voltage
Order no.: 601311
Technical Specifications | FED RJ45 10G PoE | ||
Treshold frequency core-core | f | 500 MHz | |
Insertion attenuation at 100 MHz | 1.8 dB | ||
D1 total discharge current (10/350 μs) cores-PE | Itotal | 2 kA | |
C2 nominal discharge current (8/20 μs) per core | In | 0.15 kA | |
C2 total discharge current (8/20 μs) cores-PE | Itotal | 10 kA | |
without PoE | |||
Maximum operating voltage | UC | 8.5 V DC | |
Nominal load current | IL | 0.5 A | |
C2 voltage protection level mode core-core at In | Up | 60 V | |
C3 voltage protection level mode core-core / core-PE at 1 kV/μs | Up | 22 V / 500 V | |
with PoE | |||
Maximum operating voltage | UC | 58 V DC | |
Nominal load current | IL | 1.5 A | |
C2 voltage protection level mode core-core at In | Up | 90 V | |
C3 voltage protection level mode core-core / core-PE at 1 kV/μs | Up | 80 V / 500 V | |
Response time core-core / core-PE | tA | 1 ns / 100 ns | |
Connection (input - output) | RJ45 / RJ45 | ||
Degree of protection | IP 20 | ||
Operating temperature | -40 °C … +80 °C | ||
Permissible relative humidity | RH | 5% ... 95% | |
Mounting on | 35 mm DIN rail | ||
According to standard | EN 61643-21+A1, A2:2013 / IEC 61643-21+A1, A2:2012, D1, C2, C3 | ||
Order number | 601 311 |