FE T1+T2 275 TNS 12,5 FM

4+0 Configuration

Total discharge current (Itotal) 50 kA
Voltage protection level Up < 1.5 kV
With remote indication contact

DESCRIPTION  FE T1+T2 275 TNS 12,5 FM
Nominal voltage UN230 V AC
Maximum operating voltageUC275 V AC/350 V DC
Lightning impulse current (10/350 µs)Iimp12.5 kA
Nominal discharge current (8/20 µs)In30 kA
Maximum discharge current (8/20 µs) Imax60 kA
Voltage protection level at 5kAUp0.9 kV
Voltage protection level Up1.5 kV
Short-circuit current ratingISCCR50 kA
Maximum overcurrent protection  160 A gL/gG
Response time  tA25 ns
Cross-section of connected conductors solid  1 mm2 …  35 mm2
Cross-section of connected conductors stranded  1 mm2  … 25 mm2
Fault indication with
Remote indication  potential-free change-over contact
Remote indication contacts  250 V/0.5 A AC; 250 V/0.1 A DC
Cross-section of remote indication conductors  1.5 mm2
Degree of protection  IP 20
Range of operating temperatures  -40 °C … +80 °C
Mounting  DIN rail 35 mm
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T1, T2
Order Number 565 821
Data sheet
LV-Text

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29

Email