FE T2 150 40

1+0 Configuration

Maximum discharge current (Imax) 40 kA
Voltage protection level Up < 0.7 kV

DESCRIPTION  FE T2 150 40 
Nominal voltage UN120 V AC
Maximum operating voltage UC150 V AC/200 V DC
Nominal discharge current (8/20 µs)In15 kA
Maximum discharge current (8/20 µs)Imax40 kA
Voltage protection level at 5 kAUp0.45 kV
Voltage protection levelUp0.7 kV
Short-circuit current rating ISCCR50 kA
Maximum overcurrent protection  160 A gL/gG
Response timetA25 ns
Cross-section of connected conductors solid 1 mm2 ... 35 mm2
Cross-section of connected conductors stranded 1 mm2 …  25 mm2
Fault indication with
Degree of protection  IP 20
Range of operating temperatures  -40 °C … + 80 °C
Mounting  DIN rail 35 mm
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T2
Order Number 202 120