FE T2 275 TNS 40

4+0 Configuration

Maximum discharge current (Imax) 40 kA
Voltage protection level Up < 1.5 kV

DESCRIPTION  FE T2 275 TNS 40 
Nominal voltage UN230 V AC
Maximum operating voltageUC275 V AC/350 V DC
Nominal discharge current (8/20 µs)In20 kA
Maximum discharge current (8/20 µs)Imax40 kA
Voltage protection level at 5 kAUp0.9 kV
Voltage protection levelUp1.35 kV
Short-circuit current rating ISCCR50 kA
Maximum overcurrent protection  160 A gL/gG
Response timetA25 ns
Cross-section of connected conductors solid  1 mm2 …  35 mm2
Cross-section of connected conductors stranded  1 mm2 …  25 mm2
Fault indication with
Degree of protection  IP 20
Range of operating temperatures  -40 °C … + 80 °C
Mounting  DIN rail 35 mm
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T2
Order Number 205 820
Data sheet
LV-Text

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29