FE T2 275 TT 2P 40 FM

1+1 Configuration

Maximum discharge current (Imax) 40 kA
Voltage protection level Up < 1.5 kV
With remote indication contact

DESCRIPTION  FE T2 275 TT 2P 40 FM
Nominal voltage UN230 V AC
Maximum operating voltage L-NUC275 V AC
Maximum operating voltage N-PEUC255 V AC
Nominal discharge current (8/20 µs) L-NIn20 kA
Nominal discharge current (8/20 µs) N-PEIn20 kA
Maximum discharge current (8/20 µs) L-NImax40 kA
Maximum discharge current (8/20 µs) N-PEImax40 kA
Voltage protection level at 5 kA L-NUp0.9 kV
Voltage protection level mode L-NUp1.35 kV
Voltage protection level mode N-PEUp1.5 kV
Voltage protection level mode L-PEUp1.5 kV
Follow current extinguish capability N-PEIfi100 A
Short-circuit current rating ISCCR50 kA
Maximum overcurrent protection  160 A gL/gG
Response time L-NtA25 ns
Response time N-PEtA100 ns
Cross-section of connected conductors solid  1 mm2 …  35 mm2
Cross-section of connected conductors stranded  1 mm2 …  25 mm2
Fault indication L-N with
Remote indication potential-free change-over contact
Remote indication contacts  250 V/0.5 A AC; 250 V/0.1 A DC
Cross-section of remote indication conductors  1.5 mm2
Degree of protection  IP 20
Range of operating temperatures  -40 °C … + 80 °C
Mounting  DIN rail 35 mm
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T2
Order Number 205 221
Data sheet
LV-Text

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29

Email