FE T2+T3 320 LED - 306930

Voltage protection level Up < 1.5 kV
Fault signalling by supply interruption

Technical Specifications FE T2+T3 320 LED
Nominal voltage UN230 V AC
Maximum operating voltage UC320 V AC 
Nominal load currentIL10 A
Nominal discharge current (8/20 μs) L-N / N-PE  In5 kA / 5 kA 
Maximum discharge current (8/20 μs) L-N / N-PE Imax10 kA / 10 kA
Test voltage L-N / N-PE / L-PE UOC10 kV / 10 kV / 10 kV 
Voltage protection level L-N / N-PE / L-PE Up< 1.3 kV / < 1.5 kV / < 1.5 kV
Short-circuit current ratingISCCR3 kA
Maximum overcurrent protection 32 A gG or C 32 A
TOV behavior L-N UT335 V (5 s / withstand mode)
TOV behavior L-N UT440 V (120 min / withstand mode)
TOV behavior N-PEUT1200 V (200 ms / safe failure mode)
Response time L-N / N-PEtA25 ns / 100 ns
Cross-section of connected conductors rigid (max.) 2.5 mm²
Cross-section of connected conductors flexible (max.) 1.5 mm²
Fault indication yes
Interruption of  power supply yes
Degree of protection IP 20
Operating temperature -40 °C … +80 °C
Permissible relative humidity RH5% ... 95%
Mounting in installation box
According to standard EN 61643-11:2012 / IEC 61643-11:2011 / T2, T3
Order number 306 930
Data sheet

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29

Email