FE T2+T3 320 LED

Voltage protection level Up < 1.5 kV
Fault signalling by supply interruption

DESCRIPTION  FE T2+T3 320 LED
Nominal voltage UN230 V AC
Maximum operating voltageUc320 V AC
Nominal load currentIL10 A
Nominal discharge current (8/20 µs) L-NIn5 kA
Nominal discharge current (8/20 µs) N-PEIn5 kA
Maximum discharge current (8/20 µs) L-NImax10 kA
Maximum discharge current (8/20 µs) N-PEImax10 kA
Test voltage L-NUoc10 kV
Test voltage N-PEUoc10 kV
Test voltage L-PEUoc10 kV
Voltage protection level mode L-NUp1.3 kV
Voltage protection level mode N-PEUp1.5 kV
Voltage protection level mode L-PEUp1.5 kV
Short-circuit current rating ISCCR3 kA
Maximum overcurrent protection  32 A gL/gG or C 32A
Response time L-NtA25 ns
Response time N-PEtA100 ns
Cross-section of connected conductors solid (max)  2.5 mm2
Cross-section of connected conductors stranded (max)  1.5 mm2
Fault indication loss of voltage, dark grey indication field
Degree of protection  IP 20
Range of operating temperatures  -40 °C … + 80 °C
Mounting installation box
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T2, T3
Order Number 306 930