JSB T2 3+0 275 40 FM

3+0 Configuration

Maximum discharge current (Imax) 40 kA
Voltage protection level Up < 1.5 kV
With remote indication contact

DESCRIPTION  JSB T2 3+0 275 40 FM
Nominal voltage UN230 V AC
Maximum operating voltageUc275 V AC/350 V DC
Nominal discharge current (8/20 µs)In20 kA
Maximum discharge current (8/20 µs)Imax40 kA
Voltage protection level at 5 kAUp0.9 kV
Voltage protection levelUp1.35 kV
Short-circuit current rating ISCCR25 kA
Maximum overcurrent protection  160 A gL/gG
Response timetA25 ns
Cross-section of connected conductors solid 1 mm2 ... 35 mm2
Cross-section of connected conductors stranded 1 mm2 ... 25 mm2
Fault indication with
Remote indication  potential-free change-over contact
Remote indication contacts  250 V/0.5 A AC; 250 V/0.1 A DC
Cross-section of remote indication conductors  1.5 mm2
Degree of protection  IP 20
Range of operating temperatures  -40 °C … + 80 °C
Mounting  DIN rail 35 mm
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T2
Order Number 170 006
Data sheet

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29

Email