FE T3 275 H 2P FM

Voltage protection level Up < 1.5 kV
With remote indication contact

DESCRIPTION  FE T3 275 H 2P FM
Nominal voltage UN230 V AC
Maximum operating voltageUC275 V AC
Nominal load currentIL25 A
Nominal discharge current (8/20 µs) L-NIn3 kA
Nominal discharge current (8/20 µs) N-PEIn3 kA
Nominal discharge current (8/20 µs) L+N-PEIn5 kA
Test voltage L-NUoc6 kV
Test voltage N-PEUoc6 kV
Test voltage L+N-PEUoc10 kV
Voltage protection level mode L-NUp1.2 kV
Voltage protection level mode N-PEUp1.5 kV
Voltage protection level mode L-PEUp1.5 kV
Short-circuit current rating ISCCR6 kA
Maximum overcurrent protection  25 A gL/gG or C 25 A
Response time L-NtA25 ns
Response time N-PEtA100 ns
Cross-section of connected conductors solid (max) 6 mm2
Cross-section of connected conductors stranded (max) 6 mm2
Fault indication with
Remote indication potential-free change-over contact
Remote indication contacts 250 V/0.5 A AC; 250 V/0.1 A DC
Cross-section of remote indication conductors 1.5 mm2
Degree of protection  IP20
Range of operating temperatures  -40 °C … +80 °C
Mounting DIN rail 35 mm
According to standard  EN 61643-11:2012/IEC 61643-11:2011/T3
Order Number 305 321
Data sheet
LV-Text

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29

Email