FE T3 320 LED - 306920

Surge protection especially for LED lights, installation close to protected equipment

Fault signalling by supply interruption

Order no.: 306920

Technical Specifications FE T3 320 LED 
Nominal voltage UN230 V AC
Maximum operating voltage UC320 V AC
Nominal load currentIL5 A
Nominal discharge current (8/20 μs) L-N /N-PE / L+N-PE In3 kA / 3 kA / 5 kA
Test voltage L-N / N-PE / L-PE / L+N-PEUOC6 kV / 6 kV / 6 kV / 10 kV
Voltage protection level L-N / N-PE / L-PEUp< 1.65 kV / < 1.5 kV / < 1.5 kV
Short-circuit current ratingISCCR1.5 kA
Maximum overcurrent protection 16 A gG or B 16 A
TOV behavior L-N UT335 V (5 s / withstand mode)
TOV behavior L-N UT440 V (120 min / withstand mode)
TOV behavior N-PEUT1200 V (200 ms / safe failure mode)
Response time L-N / N-PEtA25 ns / 100 ns
Interruption of  power supply yes
Degree of protection IP 20
Operating temperature -40 °C … +80 °C
Permissible relative humidity RH5% ... 95%
Mounting in installation box
According to standard EN 61643-11:2012 / IEC 61643-11:2011 / T3
Order number 306 920
Data sheet

Fuchsberg Electric GmbH

Am Fuchsberg 6

39112 Magdeburg

Phone+49 391 727699-0+49 391 727699-0

Fax+49 391 727699-29

Email