Surge protection especially for LED lights, installation close to protected equipment
Fault signalling by supply interruption
Order no.: 306920
| Technical Specifications | FE T3 320 LED | |
| Nominal voltage | UN | 230 V AC |
| Maximum operating voltage | UC | 320 V AC |
| Nominal load current | IL | 5 A |
| Nominal discharge current (8/20 μs) L-N /N-PE / L+N-PE | In | 3 kA / 3 kA / 5 kA |
| Test voltage L-N / N-PE / L-PE / L+N-PE | UOC | 6 kV / 6 kV / 6 kV / 10 kV |
| Voltage protection level L-N / N-PE / L-PE | Up | < 1.65 kV / < 1.5 kV / < 1.5 kV |
| Short-circuit current rating | ISCCR | 1.5 kA |
| Maximum overcurrent protection | 16 A gG or B 16 A | |
| TOV behavior L-N | UT | 335 V (5 s / withstand mode) |
| TOV behavior L-N | UT | 440 V (120 min / withstand mode) |
| TOV behavior N-PE | UT | 1200 V (200 ms / safe failure mode) |
| Response time L-N / N-PE | tA | 25 ns / 100 ns |
| Interruption of power supply | yes | |
| Degree of protection | IP 20 | |
| Operating temperature | -40 °C … +80 °C | |
| Permissible relative humidity | RH | 5% ... 95% |
| Mounting in | installation box | |
| According to standard | EN 61643-11:2012 / IEC 61643-11:2011 / T3 | |
| Order number | 306 920 |
Fuchsberg Electric GmbH
Am Fuchsberg 6
39112 Magdeburg
Phone+49 391 727699-0+49 391 727699-0
Fax+49 391 727699-29