3+0 Configuration
Total discharge current (Itotal) 37.5 kA
Voltage protection level (Up) < 1.5 kV
Order no.: 565620
Technical Specifications | FE T1+T2 275 TNC 12,5 | |
Nominal voltage | UN | 230 V AC / 400 V AC |
Maximum operating voltage | UC | 275 V AC |
Lightning impulse current (10/350 μs) | Iimp | 12.5 kA |
Total discharge current (10/350 μs) | Itotal | 37.5 kA |
Nominal discharge current (8/20 μs) | In | 30 kA |
Maximum discharge current (8/20 μs) | Imax | 60 kA |
Voltage protection level | Up | < 1.5 kV |
Short-circuit current rating | ISCCR | 50 kA |
Maximum overcurrent protection | 160 A gG | |
TOV behavior | UT | 335 V (5 s / withstand mode) |
Response time | tA | 25 ns |
Cross-section of connected conductors rigid | 1 mm2 ... 35 mm2 | |
Cross-section of connected conductors flexible | 1 mm2 ... 25 mm2 | |
Fault indication | yes | |
Degree of protection | IP 20 | |
Operating temperature | -40 °C … +80 °C | |
Permissible relative humidity | RH | 5% ... 95% |
Mounting on | 35 mm DIN rail | |
According to standard | EN 61643-11:2012 / IEC 61643-11:2011 / T1, T2 | |
Order number | 565 620 |
Fuchsberg Electric GmbH
Am Fuchsberg 6
39112 Magdeburg
Phone+49 391 727699-0+49 391 727699-0
Fax+49 391 727699-29