FE T2 150 40 FM - 202121

1+0 Configuration

Maximum discharge current (Imax) 40 kA
Voltage protection level (Up) < 0.7 kV
with remote indication contact

Order no.: 202121

Technical Specifications FE T2 150 40 FM
Nominal voltage UN120 V AC
Maximum operating voltage UC150 V AC
Nominal discharge current (8/20 μs) In15 kA
Maximum discharge current (8/20 μs) Imax40 kA
Voltage protection level Up< 0.7 kV
Short-circuit current rating ISCCR50 kA
Maximum overcurrent protection 125 A gG
TOV behaviorUT175 V (5 s / withstand mode)
Response time tA25 ns
Cross-section of connected conductors rigid 1 mm2 ... 35 mm2
Cross-section of connected conductors flexible 1 mm2 ... 25 mm2
Fault indication yes
Remote signalling contact potential free changeover contact
Remote contacts ratings 250 V/0.5 A AC; 250 V/0.1 A DC
Remote contacts cross-section 1.5 mm2
Degree of protection IP 20
Operating temperature -40 °C … +80 °C
Permissible relative humidity RH5% ... 95%
Mounting on 35 mm DIN rail 
According to standard EN 61643-11:2012 / IEC 61643-11:2011 / T2
Order number 202 121
Data sheet