3+0 Configuration
Maximum discharge current (Imax) 40 kA
Voltage protection level (Up) < 1.35 kV
with remote indication contact
Order no.: 205621
Technical Specifications | FE T2 275 TNC 40 FM | |
Nominal voltage | UN | 230 V AC / 400 V AC |
Maximum operating voltage | UC | 275 V AC |
Nominal discharge current (8/20 μs) | In | 20 kA |
Maximum discharge current (8/20 μs) | Imax | 40 kA |
Voltage protection level | Up | < 1.35 kV |
Short-circuit current rating | ISCCR | 50 kA |
Maximum overcurrent protection | 125 A gG | |
TOV behavior | UT | 335 V (5 s / withstand mode) |
TOV behavior | UT | 440 V (120 min / safe failure mode) |
Response time | tA | 25 ns |
Cross-section of connected conductors rigid | 1 mm2 ... 35 mm2 | |
Cross-section of connected conductors flexible | 1 mm2 ... 25 mm2 | |
Fault indication | yes | |
Remote signalling contact | potential free changeover contact | |
Remote contacts ratings | 250 V/0.5 A AC; 250 V/0.1 A DC | |
Remote contacts cross-section | 1.5 mm2 | |
Degree of protection | IP 20 | |
Operating temperature | -40 °C … +80 °C | |
Permissible relative humidity | RH | 5% ... 95% |
Mounting on | 35 mm DIN rail | |
According to standard | EN 61643-11:2012 / IEC 61643-11:2011 / T2 | |
Order number | 205 621 |