Combination of coarse and fine protection for video circuits
for protecting of video systems, CCTV, etc. for overvoltage.
Order no.: 602121
| Technical Specifications | FED KOAX BNC 90 F/F | |
| Maximum operating voltage | UC | 29.1 V DC |
| Nominal load current | IL | 4 A |
| C2 nominal discharge current (8/20 μs) core-PE | In | 1.5 kA |
| C3 voltage protection level mode core-PE at 1 kV/μs | Up | 80 V |
| Response time core-PE | tA | 1 ns |
| Wave impedance | Z | 75 Ω |
| Insertion attenuation | 1 dB | |
| Standing wave ratio | 1.7 | |
| Bandwidth | 1 MHz ... 2150 MHz | |
| Connection (input - output) | BNC 75 | |
| Degree of protection | IP 20 | |
| Operating temperature | -40 °C … +80 °C | |
| Permissible relative humidity | RH | 5% ... 95% |
| Mounting on | 35 mm DIN rail | |
| According to standard | EN 61643-21+A1, A2:2013 / IEC 61643-21+A1, A2:2012, C2, C3 | |
| Order number | 602 121 |